STD Transformer’s shunt reactors absorb capacitive reactive power from overhead transmission lines and underground cable networks. They help control voltage rise when circuits are lightly loaded and support voltage management at substations and grid connection points. The range extends up to 50 MVAr and up to 170 kV, with each reactor specified for the electrical, mechanical and environmental requirements of its installation.
| Parameter | Configuration |
|---|---|
| Reactor type | High-voltage shunt reactor |
| Maximum reactive power rating | Up to 50 MVAr |
| Maximum voltage level | Up to 170 kV |
| Installation | Outdoor substation applications |
| Design configuration | Specified to suit project electrical, mechanical and environmental requirements |
The required combination of reactive power rating and voltage level is confirmed for each project.
Overhead transmission lines and underground cables generate capacitive reactive power when energised. When the circuit carries a light load, this charging effect can raise the voltage at points along the network. A shunt reactor draws inductive reactive power to offset part of that effect and helps keep voltage within the network operator’s specified limits.
The reactor rating is determined from the network study. Line or cable characteristics, operating voltage and expected loading conditions all influence how much compensation the system needs. A long transmission route may require compensation during periods of low demand. A cable connection may need compensation when the cable is energised and the equipment it serves is operating at reduced output. The study also helps determine where the reactor should connect to the network.
The design starts with the required compensation in MVAr and the electrical characteristics of the connection point. Core and winding design, insulation coordination and terminal arrangements are developed around these requirements. The purchaser can also specify limits for losses and sound levels where these affect operating costs or siting.
Mechanical design takes account of the outdoor installation environment and the space available in the substation. Terminal positions, overall dimensions and accessory locations are coordinated with the site layout. For an extension to an existing substation, the design review can use the available bay drawings to identify constraints on clearances, connections and access before the equipment layout is finalised.
A shunt reactor can be connected at a line terminal or to a substation bus, depending on where the network requires compensation. The connection point and the operating conditions under which the reactor will be energised should be identified in the project specification. Where the network design calls for switching, the reactor requirements are coordinated with the associated switchgear, protection and controls.
The project team should identify which monitoring and protection signals the substation needs. Addressing these interfaces during technical review helps define accessory requirements and provides a basis for coordinating wiring, alarms and equipment drawings.
The purchase specification should identify the applicable standards, factory test scope and acceptance criteria. Any purchaser witness requirements and requested reports can be agreed during technical review so that the test documentation addresses the requirements of the supplied unit.
The project datasheet records the agreed reactive power rating, voltage and configuration. The general arrangement drawing shows the overall dimensions, terminal positions and accessory locations. These documents give the substation team the information it needs to check equipment interfaces and plan installation.
The required MVAr rating is determined from a network study that considers operating voltage, line or cable characteristics, load conditions and the voltage limits at the connection point.
Yes. Both generate capacitive reactive power when energised. The amount of compensation and its location depend on the circuit characteristics and the network’s operating requirements.
The product range extends up to 50 MVAr and up to 170 kV. The exact rating and voltage combination is confirmed during the technical review.
Share the required MVAr rating, system voltage, frequency, connection point and expected operating conditions. Include the single-line diagram, site layout, applicable standards and any limits on losses or sound levels if available.
For detailed specifications and performance information, please contact us. Our engineering team is ready to support you with your project-specific requirements.