STD Transformer’s hermetically sealed distribution transformers use a closed tank to keep the insulating liquid isolated from ambient air during normal operation. They are designed for medium-voltage distribution networks that supply low-voltage loads in utility, commercial and industrial installations. The tank, electrical connections and protection accessories are configured to suit the transformer rating and the requirements of the installation.
| Parameter | Configuration |
|---|---|
| Transformer type | Oil-immersed distribution transformer |
| Tank design | Hermetically sealed tank with corrugated walls |
| Liquid expansion | Flexible corrugated walls or a nitrogen cushion, depending on the design |
| Tap changer | Five-position off-circuit tap changer |
| High-voltage bushings | DIN 42531 or EN 50180, as applicable |
| Low-voltage bushings | DIN 42530 or EN 50386, as applicable |
| Monitoring and protection | Thermometer pocket, pressure relief valve and configuration-specific monitoring accessories |
The insulating liquid expands as the transformer warms under load and contracts as it cools. In the standard corrugated tank design, the walls flex to accommodate these changes in volume. This allows the liquid to expand and contract inside the sealed tank while remaining isolated from ambient air.
The corrugated walls also provide surface area for heat dissipation. Tank geometry and cooling surfaces are selected to suit the rating and operating conditions. For configurations that use separate radiators, or where the tank design calls for a different way to accommodate liquid expansion, a nitrogen cushion can be used while retaining the hermetically sealed arrangement.
Each transformer is specified around the supply voltage, required secondary voltage and load to be served. The selected high- and low-voltage bushings provide the connection points for the installation. Terminal orientation and connection clearances should be reviewed alongside the site layout, particularly where the transformer is installed close to switchgear or within a compact substation.
The standard five-position off-circuit tap changer allows the voltage ratio to be set to suit local supply conditions. The tap setting is selected during commissioning or adjusted when operating requirements change. Tap changes are made with the transformer de-energised.
A pressure relief valve and a thermometer pocket are included in the catalogue’s standard configuration. Depending on the rating and monitoring requirements, the transformer can be equipped with a contact thermometer or a hermetic protection relay. A suitably configured hermetic relay can provide indications for gas accumulation, internal overpressure and excessive oil temperature.
Lifting lugs, earthing terminals and a rating plate support handling, installation and identification. The catalogue also lists an oil filling plug, a drain valve and bidirectional rollers. Accessory selection should account for the site’s maintenance access and any signals that need to be connected to the substation’s alarm or protection system.
Hermetically sealed transformers are used at distribution points where medium-voltage supply is stepped down for local loads. Typical applications include public distribution substations, industrial facilities, commercial developments and compact substations.
The project specification should account for the load profile, ambient conditions, available installation space and cable entry arrangement. For a compact substation, access for cabling, inspection and handling should be checked alongside the transformer’s footprint. For industrial installations, details of the connected loads and expected operating pattern help define the electrical and thermal requirements.
STD Transformer tests transformers before dispatch in accordance with the applicable IEC 60076 requirements and the agreed project specification. The test scope is established for the unit, with additional tests specified where required by the purchaser.
Project documentation includes the technical drawing, test report and maintenance instructions. The technical drawing is used to verify installation dimensions, terminal positions and accessory locations. The project datasheet records the agreed ratings, losses and configuration for the transformer supplied.
In the standard design, corrugated tank walls flex as the insulating liquid expands and contracts. A nitrogen cushion can be used in configurations that require a different expansion arrangement
A hermetically sealed design accommodates changes in liquid volume within a sealed system. A conservator-type transformer uses a separate expansion vessel connected to the main tank. Installation space, cooling arrangement and the project’s operating requirements help determine the choice.
The standard five-position tap changer is an off-circuit device. The transformer must be de-energised before the tap position is changed.
Provide the required power rating, primary and secondary voltages, frequency, installation location and any specified loss limits. Include the preferred cable entry, monitoring accessories and applicable standards if they are already defined.
Dimensions are confirmed on the project drawing. No-load losses, load losses and other agreed electrical values are recorded in the project datasheet.
For detailed specifications and performance information, please contact us. Our engineering team is ready to support you with your project-specific requirements.